Penta Infra HAM01 – Propane-Based Cooling for a Hamburg Colocation Data Center

Efficient and Environmentally Friendly Cooling for a Medium-Sized Colocation Data Center Penta Infra broke ground in September 2023 on a new 4.4 MW colocation data center in Hamburg, Germany, near the airport. The facility, named HAM01, opened in the first half of 2025 and provides 2,500 m² of IT space. Six Secon R290 air-cooled liquid chillers were installed on the roof, delivering reliable cooling performance with high energy efficiency (EER 4.15 @ +40 °C). Next to 4 of the 6 chillers, 4 Secon dry-coolers are located. The 4 chillers with separate dry coolers are equipped with additional integrated hydraulic equipment to seamlessly integrate the dry coolers into the operation. In full free cooling mode, the heat is transferred directly to the ambient air without activating compressors. In addition the dry coolers can be integrated as pre-cooling before entering the evaporators of the chillers. Up to 80 % of annual operating hours can be covered without activating the chillers, significantly reducing energy consumption and supporting a low Power Usage Effectiveness (PUE). The system is designed to meet the German Energy Efficiency Act (EnEfG) requirements and provides operational redundancy, safety features, and flexibility for future integration with district heating networks.